This procedure describes how to power up the Main Electrical Panel and the Drive/Absorber Panel
located on the mezzanine above the Test Stands.
Power to these panels is supplied through the (E-1) STATION MAIN DISCONNECT mounted to
the side of the station's safety enclosure. This should be turned on prior to performing this procedure.
PROCEDURE:
-
Locate
the Main Electrical Panel and the Drive/Absorber Panel on the mezzanine for the Test Stand you would like to power up.
- Check the Ground Lights on the front of the Main Electrical Panel Door.
NOTE: If these light are on, the (E-3) MAIN PANEL AUXILIARY DISCONNECT located inside the cabinet is already turned on.
- If these Ground Lights are OFF. Open the right Main Electrical Panel Door to access the (E-3) MAIN PANEL AUXILIARY DISCONNECT located inside.
- Remove any lockout devices from the (E3) MAIN PANEL AUXILIARY DISCONNECT.
- Turn the (E-3) MAIN PANEL AUXILIARY DISCONNECT to the ON position. The interior panel lights and the two Ground Lights on the panel door will come on.
- Close and latch the Main Electrical Panel Door.
- Remove any lockout devices from the (E-2) MAIN PANEL MAIN DISCONNECT.
- Push the Test Stand's (E-2) MAIN PANEL MAIN DISCONNECT up to the ON position. All lights on the front of the Main Electrical Panel Door should be on.
-
Open the
DRIVE/ABSORBER PANEL right door to access the (E-5) DRIVE/ABSORBER PANEL AUXILIARY DISCONNECT located inside.
-
Remove any lockout devices from the
(E-5) DRIVE/ABSORBER PANEL AUXILIARY DISCONNECT.
-
Turn the
(E-5) DRIVE/ABSORBER PANEL AUXILIARY DISCONNECT to the ON position. The interior panel lights will come on.
-
Remove any lockout devices from the
(E-4) DRIVE/ABSORBER PANEL MAIN DISCONNECT.
-
Push up the Test Stand's
(E-4) DRIVE/ABSORBER PANEL MAIN DISCONNECT to the ON position. The Test Stand's mezzanine panels are powered up.